(c) Design Stresses. --The maximum stresses used for design were based, in general, on the following criteria: (1) Tensile. --The allowable design stresses in tension used for the following materials were the lower value of the percentages of the yield and ultimate strength of the material: (2) Compression. -- The allowable design stress in compression used for the materials listed above were the same as for tension. (3) Shear. -- The allowable design stresses in shear were not more than 0.6 of the allowable design stresses in tension. (4) Structural steel. -- The allowable design stresses for structural steel in tension or compression were not more than 20,000 pounds per square inch. In general, GENERAL OPERATING INFORMATION A. PURPOSE AND OPERATION: 1. Two 16.75 x 34 foot fixed wheel gates are provided to regulate spillway 2. Each gate will be opened, stopped or closed with unbalanced pressures 4. A power interruption when the gate is open, stopped, closed or closing 5. Gate position in feet is indicated for each gate in the control cabinet. NOTE: For the electrical schematic and wiring diagrams, see inside of Electrical compartment door. JIC HYDRAULIC SCHEMATIC B. OPERATING INSTRUCTIONS: 1. General a The hanger yoke must be in a vertical position for gate operation. The hanger stud is engaged for servicing only. b. Prior to normal operation of the gates, the hydraulic valves should be set as follows: (1). Valves J,. J. K,, K2. H. L ond M-- fully open. (2) Valves A, A2, B1, B2, U,, U2. V. V2. W. X,. X2.Y,.Y2, Z. D. R,, R2 and N--fully closed. (3).4-Way valve--in neutral position. c. Oil level in tank should be at "LOW level for both gates open and "HIGH level for both gates closed. d. The oil pressure switch, relief valves and unloading valves should have been previously adjusted as specified under the Installation and Servicing Instructions, Paragraph D. Place 4-way valve in NEUTRAL). 4. To stop gate No.1 or No. 2: a. Shift 4-way valve to NEUTRAL. b. Close valves A, and B, or A2 and B2. c. If gate is opening, press STOP push button. 5. To reverse travel of gates: a. Shift 4-way valve to NEUTRAL. b. Press STOP push button if gate is opening or press RUN push button if gate is closing. c. Shift 4-way valve to OPEN or CLOSE as required. Figure 67. -16.75 by 34-foot fixed-wheel gate hoists control --Operating diagrams and instructions. (Sheet 1 of 2.) From drawing No. 591-D-1353. INSTALLATION AND SERVICING INSTRUCTIONS A. GATE AND HOIST INSTALLATION: 1. The gates should be assembled on the erection beams as shown on Dwg. 591-0-887, Invitation No. DS-5632 and the hoists and controls installed as shown on Dwgs. 591-D-1043 and 1260, Invitation No. DS-5662 and (D) 90088-A, respectively. Each hoist cylinder assembly should be installed with the piston, piston stem and sheave block supported by the hanger stud. 2. Service the hoists and control cabinet in accordance with Paragraph 3. Lower the sheave block, 1044-37,of each hoist (by opening appropriate 4. Operate the hoists, as outlined in Paragraph B of General Operating 5. Lower each gate until it seats on the spillway crest and adjust 6 Operate each gate through several complete opening and closing cycles. Readjust eyebolts to maintain the 4 dimension of Step 5. B. FILLING THE SYSTEM WITH OIL: 1. It is assumed each hoist is installed as instructed in the preceding 2. Approximately 800 gallons of new, clean, light hydraulic oil is 3. Perform the following preliminary steps: a. Visually check the dial settings of pressure switch PS for agreement with values listed in the following Subparagraph D-3. b. Open all hand-operated valves in the system (A,. Az. B. B2. H, J, J. K. K2. L. M. U,, U2. V1. V2. W. X1, X2. Y. Y2 and Z), except valves D. N, R, and R, which should be closed. c. Adjust relief valve E to open at minimum pressure. d. Fill the oil tank to the LOW level on the sight gage and maintain this level during the filling operation. 4. To fill the hoist cylinder and hydraulic lines: a. Crack the two air vent plugs Q in the pump suction line until air b. Shift 4-way valve to OPEN and press RUN push button to start pumps c. Shift 4-way valve to NEUTRAL position. Close valve M and open valves Z and N. After a few minutes, close valves w then N, open valve M and then close valves Z. Y, and Y2 in succession. d. Shift 4-way valve to CLOSE position and continue to fill lower parts 5. Check and adjust relief valves E and F, unloading valve G,. and 6. Operate each hoist separately through several cycles to remove air a. Open appropriate valves A, and B, or A, and B. Press RUN push c. Shift 4-way valve to CLOSE position and restart pumps to raise C. POSITION INDICATOR INSTALLATION AND ADJUSTMENT: Install indicator parts and reeve cobles as shown on Dwgs 591-D-1260 and 1265 2 With the gates seated and the pistons against the upper cylinder heads, adjust the indicator cables until the pointers are inch below the CLOSED position, Bottom of counterweights, 1265-7c, should be approximately inch from stop, 1262-238. D. PRESSURE DEVICES--FUNCTIONS, SETTINGS, AND ADJUSTMENTS: 1. Relief valve E limits maximum system pressure whereas relief valve a. Relief valve E should be adjusted as follows: (1)Set pressure switch PS to open contacts at 1,100 psi using the calibrated adjusting screw on the switch. (2)With valves 8, and B, closed, shift 4-way valve to CLOSE (3) Adjust relief valve E to obtain a gage pressure of 1000 psi. b. Relief valve F should be adjusted as follows: (1) Open valve N and close valve M. (2) With valves B, and B, closed, shift 4-way valve to NEUTRAL position and press RUN push button. (3) Adjust relief valve F to obtain a gage pressure of 100 psi. 2. The unloading valve G operates when opening the gates to return a. With valves B, and B, closed, shift 4-way to NEUTRAL and press b. Adjust relief valve F to obtain a goge pressure of approximately 600psi. a With valves B, and B2 closed, close valve M and shift 4-way valve b. Using valve M as a throttle, adjust pressure switch contacts to open at 4 The flow control valve automatically throttles the oil to maintain a E. MAINTENANCE: 1. The service and maintenance procedures recommended by the manufacturer shall be followed for all commercial components. 2. The oil tank and cylinders shall be drained of accumulated sediment annually through drain valves D, R. and R2 3. The oil filter should be removed and cleaned immediately after the gates are installed, and thereafter at 1-year intervals, as follows: a. Close valve L, remove and clean filter. b. Replace O-ring and reassemble filter. c. Loosen the two vent plugs Q on either side of filter and crock valve L 4. Inspect and lubricate the position indicator mechanisms annually. 5. All wire ropes and sockets should be inspected annually for deteriorating 6. All wire ropes should be wire brushed and lubricated annually, or more 7. The sheave bearings should be lubricated annually with Lubriplate 630AA 8. During the first year following installation, operate each gate through 9. Every 3 years remove and check the oil pressure gage for accuracy and 10 After approximately 5 years of service, one gate should be raised, supported on the erection beams and the following maintenance performed: b. Check seals for damage and flexibility of movement and repair or c. Check guide shoe springs and rubbing plates for freedom of movement and damage. Repair as necessary. d. Repair damaged areas of paint on gate and equalizer connections e. Based on the repairs required and the condition of the gate at this 11. The piston packing may be replaced as follows: a. Lower gate requiring new piston packing to fully closed position A, and B, or A2 and B2 open. Press RUN push button. After pumps b. Disconnect piping and remove upper cylinder head. Provide means c. Remove packing gland and old packing. d. Install new packing and replace packing gland. Install new o-ring e. Open appropriate valves A,, B,, J, K, and U, or A2, B2. J2. K2 and U2 f. When all air has vented, close valve U, or U2 and place gate at g. Replace oil in tank, if required. Figure 67.-16.75- by 34-foot fixed-wheel gate hoists control --Operating diagrams and instructions. (Sheet 2 of 2.) From drawing No. 591-D-1353. structural steel stresses were based on the American Institute of Steel Construction "Specification for the Design, Fabrication and Erection of Structural Steel for Buildings," 1961. (5) Hoist cylinders. --The allowable design stresses for the hoist cylinders were based on the recommendations of the ASME Boiler and Pressure Vessel Code -- Unfired Pressure Vessels Section, 1962. 57. General. The criteria for determining the size of the outlet works was for the conveyance system to be of sufficient capacity to be capable of returning to the river in a 12-month period, the entire annual flow of the maximum year of record (approximately 2.6 million acre-feet in 1950) excepting 40,000 acre-feet of absolute dead storage below the centerline of the outlet pipes. The invert of the river outlets was established at elevation 5740.0 which was the minimum pool required to accommodate about 200 years of sediment inflow. The outlets were originally required to also meet the following criteria: Required capacity, second-feet 3,000 Reservoir elevation, feet 5790 5935 To avoid excessive velocities in the outlet pipes, a criterion was established limiting the maximum discharge of each outlet to 2,000 second-feet, except in an emergency, regardless of the reservoir head. 58. Selection of Location. Details of the outlet works are shown on figures 68 and 69. The river outlets consist of two 72-inch-diameter pipes which extend through the dam to a gate structure, located at the toe of the dam, to the left of the powerplant building. The pipes reduce in size at the lower end of the elbow to 66 inches in diameter and extend to the 66-inch ring-follower emergency closure gates, located in the gate structure at the toe of dam. The pipes then extend downstream, beneath the powerplant service area, for approximately 200 feet, at which point 66-inch hollow-jet valves regulate the discharge into the river downstream of the powerplant tailrace. The downstream portions of the pipes have been encased in reinforced concrete. Overbreak in excavation, as well as poor and shattered rock, necessitated the construction of a support structure to provide a base for the concrete-encased outlet pipes. A semicircular trashrack structure protects the intakes of the two outlet pipes at the upstream face of the dam. A bulkhead gate, operated by a gantry crane at the top of the dam, will provide closure at the upstream face of the dam of either pipe for maintenance or inspection. Provisions are provided to gain access to the pipes through manholes from an adit in the dam. 59. Reinforcement. The following assumptions or procedures were used in designing the reinforcement around the outlet pipes: (1) For pipe embedded in the mass concrete of the dam, no bursting pressure was assumed, except for the bellmouth at the intake and for a portion of the pipe at the downstream face of the dam. (2) Temperature differential acting in combination with live load dam stresses was assumed as follows: Varies linearly from 0° F. at upstream face to 5° F. at P.I. of top bend; 5° F. differential between P.I. of top bend and P. C. of bottom bend; Varies linearly from 5° F. at P. C. of bottom bend to 10° F. at downstream face of dam; and Temperature differential of 5° F. for entire length of pipe when combined with dead load dam stresses. |