OUTLINE DRAWINGS--SPECIAL NOTES Fig. 3 Par. 4.4C OUTLINE DRAWINGS SPECIAL NOTES (Examples of special notes to be placed on each drawing to which they may apply.) The bottom slab shall be placed on thoroughly compacted earth or backfill. Light steel-trowel finish top of structural slab to El..... Note for deck and Cross hatching indicates area to be wood-float finished. For location of generator partition and curbs see Terrazzo Finish drawings. Place tie-to inserts in the bottom of the slab @3:0"centers in the area between reference lines to and to except in the stairway slab. (Above note for areas to support suspended metal lath and plaster ceilings.) Existing concrete to be removed to elevations shown. (on alteration dwgs.) New concrete shall have an ultimate compressive strength of not less than [4000] lbs. per sq. in. Care shall be taken in the construction of the walls and floor of the sump to obtain as impervious concrete and tight joints as possible in order to reduce leakage to a minimum. Extra care shall be taken to obtain true and smooth contact surfaces for draft tube gates to insure tight seating of gates. (On all floor plans which are to receive an applied finish place the following note on each area of different slab thickness.) Top of [12] rough slab El. 11⁄2"finish. (Use top of finish El. in drawing title as: Floor El. 1012.50) (All untraced drawings issued to the field shall have a note defining its status. REV. 8-19-50 FORMERLY X-D-3619 103-D-222 Fig. 4 Par. 4.4E REINFORCEMENT--DRAWING NOTES REINFORCEMENT - DRAWING NOTES. The following notes are to be put on a key sheet, such as the first floor plan,and located above the title block. Repeat on each set of dwg's., such as the Service Bay, Control Bay, etc., but only on the Substructure of each set unless the Intermediate or Superstructure is to be built by another contractor, in which case repeat on lowest plan. Comments below in parentheses () are not to be copied. (General) NOTES All bent bars to have prefix letter to number given. (R For Control bays; P for Main Only for buildings with expansion joints. All dimensions to a joint are to the center line of the joint. t.f. indicates top face; b.f. bottom face; t.r.,top row; b.r., bottom row. (Slabs, beams, etc.) Reinforcement may be moved as necessary to clear pipes, seals, recesses, embedded metalwork, and conduits except in heavily reinforced areas, as for example bars at minimum spacing in main crane columns. For other embedded metalwork not shown, such as seals, pipes, sleeves, conduits, (To the above general notes add such of the following notes as may apply.) Use small-size scrap reinforcement for spacer ties for inner rows of beams and columns. (The following note is to be placed on all reinforcement dwg's except the key sheet.) For general notes and reference drawings see................(refer to key sheet.) No reinforcement to be placed between conduits in Floor El...- - - -- Dowels shown on this dwg. are to be grouted into drilled holes which are located on dwa... Vertical dowels shown on this sheet shall be deformed bars of [hard] grade billet steel. For location of (79) anchors (PIOC5) for draft tube liner see Dwg......D...... Vertical bar lengths in the walls and columns are based on the elevations shown on excavation Drawing...D........ If excavation is deeper, bar lengths should be increased accordingly. REV. 4-7-49 FORMERLY X-D-3620 103-D-223 Min. TYPE "F" DETAIL DETAIL "H" ANGLE AND BULB TO BACK CONNECTIONS -Remove bulb, buff contact surfaces, and apply rubber cement -Type D DETAIL "R" (An Alternate for Butt Splices) Metal seal, (See Detail "S" and Section 4) Machine bolts, stainless steel --Metal seal, Type "N" DETAIL ' 3 Spc. @2"--- 4-16 Goge stainless PLAN -Coat contact surfaces with rubber cement SECTION TYPICAL SPLICES Metal seal Type "N" RUBBER WATERSTOPS TO METAL SEALS SECTION 5 NOTES For all contact surfaces, remove neoprene coating, except where Connection of these waterstops to type "N" metal seal is made |